Which MCB do I need? Rating, curve and poles explained

How to pick the MCB rating, trip curve and number of poles for lights, sockets, ACs, geysers and three-phase circuits.

Quick answer

Choose an MCB rated at or just above the circuit's normal current, but never above what the wire can carry. Use a C curve for most circuits, B for lighting and D for motors. Use DP (2 pole) where both phase and neutral must switch off, such as for an AC or geyser.

Typical MCB ratings for a home or shop

CircuitTypical loadMCBCopper wire
Lighting and fansup to about 1 kW6 A or 10 A, B curve, SP1.5 sq mm
Power sockets (16 A)up to about 3 kW16 A, C curve, SP2.5 sq mm
Geyser, 2 kWabout 8.7 A16 A, C curve, DP2.5 sq mm
Geyser, 3 kWabout 13 A20 A, C curve, DP4 sq mm
Split AC, 1.5 tonabout 7–8 A running16 A, C curve, DP2.5 sq mm
Split AC, 2 tonabout 9–10 A running20 A, C curve, DP4 sq mm
Three-phase distributiondepends on loadTP or 4 pole, C curveas per load

1. The rating (amps)

Work out the current: for a single-phase load, current ≈ watts ÷ 230. A 2 kW geyser draws about 2000 ÷ 230 = 8.7 A, so a 16 A MCB suits it. The MCB protects the wire, so its rating must never be higher than the wire's safe current. If you need a bigger MCB, you need a bigger wire too.

2. The trip curve (B, C or D)

CurveTrips instantly atUse for
B3 to 5 × rated currentLighting and resistive loads such as heaters
C5 to 10 × rated currentGeneral circuits, sockets, ACs, small motors: the usual choice
D10 to 20 × rated currentMotors, transformers, welding sets and loads with high starting current

3. The number of poles

TypePolesUse
SP1 poleSingle-phase circuits, switching the phase only
DP2 poleSingle-phase, switching phase and neutral: AC, geyser, incomer
TP3 poleThree-phase loads without neutral, such as motors
TPN / FP3 pole + neutral / 4 poleThree-phase distribution with neutral

4. Breaking capacity

This is the largest fault current the MCB can safely break, marked in kA. 6 kA suits most homes; 10 kA is the usual choice for commercial buildings and industry, especially close to a large transformer.

Add an RCCB for shock protection

An MCB does not protect people from electric shock. Add a 30 mA RCCB on the incoming supply, or on wet-area circuits such as the bathroom and kitchen. 100 mA and 300 mA RCCBs are used for fire protection on larger installations.

MCBs and RCCBs we supply

Need help choosing?

Send us the rating, the load or a photo of the nameplate on WhatsApp, and we will confirm the right model, availability and rate.

Values are typical guidance for Indian 230 V single-phase and 415 V three-phase supplies. Always follow the equipment nameplate, the manufacturer's instructions and your licensed electrician, who is responsible for the final selection and installation.

FAQ

Questions

Which MCB is used for a 1.5 ton AC?

Usually a 16 A, C curve, double pole (DP) MCB with 2.5 sq mm copper wire. Check the AC's manual, as some models ask for 20 A.

What does 'C curve' mean on an MCB?

It is the tripping speed on a current surge: C curve trips instantly at 5 to 10 times its rating, which suits most circuits.

Can I use a bigger MCB if it keeps tripping?

No. The MCB protects the wire. Find the reason it trips: an overload, a fault or the wrong curve. A bigger MCB on the same wire can let the wire overheat.