How to size a capacitor for power factor correction

Work out the kVAr needed to raise your power factor, then choose between fixed capacitors and an APFC panel, and the right duty and voltage.

Quick answer

Capacitor kVAr = load kW × multiplier from the table below. For a 100 kW load at 0.80 power factor, raising it to 0.95 needs 100 × 0.42 = about 42 kVAr.

Multiplier table

Find your present power factor on the left and the target at the top; multiply your load in kW by the figure.

Present PFTarget 0.95Target 0.98Target 0.99
0.700.690.820.88
0.750.550.680.74
0.800.420.550.61
0.850.290.420.48
0.900.160.280.34

The figures are tan φ₁ − tan φ₂ for the two power factors. Your electricity bill or a power analyser shows the present power factor and the maximum demand in kW.

Fixed capacitors or an APFC panel?

A fixed capacitor suits a steady load, such as a single large motor, connected after its starter. Where the load changes through the day, an automatic power factor correction (APFC) panel switches capacitor steps in and out with capacitor duty contactors, keeping the power factor close to the target without over-correcting.

Choosing the capacitor

Your networkCapacitor duty
Mostly motors and lighting, few drivesStandard duty
General industry, frequent switchingHeavy duty or gas-filled heavy duty plus
Drives, UPS, inverters (harmonics), heavy switchingLTXL ultra heavy duty, often with detuned reactors

On a normal 415 V supply, 440 V capacitors are the usual choice. Where detuned reactors are used or the voltage runs high, 480 V or 525 V capacitors are chosen. Switch each step with a capacitor duty contactor, such as the L&T MO C, which limits the inrush current.

Capacitors we supply

Need help choosing?

Send us the rating, the load or a photo of the nameplate on WhatsApp, and we will confirm the right model, availability and rate.

Values are typical guidance for Indian 230 V single-phase and 415 V three-phase supplies. Always follow the equipment nameplate, the manufacturer's instructions and your licensed electrician, who is responsible for the final selection and installation.

FAQ

Questions

How many kVAr capacitor do I need for 100 kW?

It depends on the present and target power factor. From 0.80 to 0.95 you need about 42 kVAr; from 0.85 to 0.95 about 29 kVAr.

Can too much capacitance cause problems?

Yes. Over-correction gives a leading power factor and high voltage at light load. An APFC panel avoids this by switching steps to match the load.

Why use 440 V capacitors on a 415 V supply?

The extra margin covers supply voltage variations and harmonics, which helps the capacitor last longer.