Delivering pan India · Since 2002 · GST invoicing
Quote list0
Buying guide

Why does my MCB or RCCB keep tripping?

A tripping breaker is doing its job. Here is how to find out why it trips, and when the breaker itself needs replacing.

Quick answer

If an MCB trips after running a while, the circuit is usually overloaded; if it trips instantly, look for a short circuit. If an RCCB trips, something is leaking current to earth, often a geyser, an appliance or damp wiring. Never hold a breaker on or replace it with a bigger one.

MCB tripping: common causes

What you seeLikely causeWhat to do
Trips after some minutes or hoursOverload: too many appliances on one circuitMove loads to another circuit, or have the circuit upgraded with bigger wire and MCB
Trips instantly when switched onShort circuit in the wiring or an applianceUnplug everything; if it still trips, the fault is in the wiring: call an electrician
Trips when a motor, pump or AC startsStarting current too high for a B curve MCBA C curve MCB of the same rating usually suits; D curve for motors
MCB is hot, or trips at light loadLoose terminal or an old, weak MCBHave the connections tightened, or replace the MCB

RCCB tripping: common causes

What you seeLikely causeWhat to do
Trips when the geyser or an appliance switches onLeakage in that appliance, often a geyser elementUnplug it and test the RCCB again; have the appliance repaired
Trips in the monsoon or after rainMoisture in outdoor points, junction boxes or old wiringFind and dry or seal the wet point
Trips at random, nothing obviousNeutrals of different circuits mixed, or many small leakagesAn electrician should check that each RCCB has its own neutrals
Will not reset at all, even with nothing connectedFaulty RCCB or a wiring faultHave it tested; replace if faulty

Finding the cause safely

  1. Switch off or unplug every appliance on the circuit.
  2. Reset the breaker. If it trips with nothing connected, the fault is in the wiring: stop here and call an electrician.
  3. Switch the loads on one at a time. The one that trips it is the culprit.
  4. Press the RCCB's T (test) button once a month: it should trip. If it does not, replace the RCCB.

Products

Need help choosing?

Send us the rating, the load or a photo of the nameplate on WhatsApp, and we will confirm the right model, availability and rate.

Values are typical guidance for Indian 230 V single-phase and 415 V three-phase supplies. Always follow the equipment nameplate, the manufacturer's instructions and your licensed electrician, who is responsible for the final selection and installation.

FAQ

Questions

Can I replace a tripping 16 A MCB with a 32 A one?

No. The MCB protects the wire. A bigger MCB on the same wire can let it overheat and cause a fire. Find the reason it trips instead.

Why does my RCCB trip when the geyser is on?

Usually the geyser's heating element is leaking current to earth. Have the element checked and replaced.

How long does an MCB last?

Many years, but after repeated heavy trips or heating it can become weak and trip early. Replace it if it trips at normal load or feels hot.

Get a quote

Have a list, a BOQ or a nameplate photo?

Send it on WhatsApp or email and we'll reply with availability and rates.

WhatsApp